Impact of Solar PV Penetration on Overcurrent Relay Coordination in Radial Distribution Networks
- 1 Department of Electrical and Computer Engineering, Faculty of Engineering, King Abdulaziz University, Jeddah 21589, Saudi Arabia
- 2 Department of Electrical and Computer Engineering, Faculty of Engineering, King Abdulaziz University, Jeddah 21589, Saudi Arabia
Abstract
The trend on the growth of the installation of solar photovoltaic (PV) systems in the current radial distribution networks radar has altered the system protection dynamics largely. This paper examines the quantitative effects of different PV penetration rates on over current relay (OCR) coordination in a system of differing grid strengths strong, medium, and weak by short circuit and relay coordination of MATLAB simulations. Two models of inverters INV1.2 and INV2.0 were used in order to test how the limit of current in inverters affects the performance of protection. The suffix indicates the per-unit limit of the short-circuit current contribution of the inverter to its actual current. In particular, the maximum current of faults is limited to 1.2 p.u. by INV1.2 and to 2.0 p.u. by INV2.0 before being saturated. Such limits attempt to reproduce the protection type logic of a current-day grid-following inverter when there is a fault. The inverter current-limiting models are represented by the acronyms INV1.2 and INV2.0, in which the short-circuit contribution of the inverter is limited to 1.2 and 2.0 per-unit of rated current give or take. INV1. The findings indicate that fault current in robust grids had risen by 55 per cent (5.1 kA to 7.9 kA) and in weak grids by −20% (5.1 kA to 4.1 kA) with 100 % penetration of PV. The coordination time interval (CTI) between primary and backup relays decreased to a value of 0.18 s, which means that selectivity is partially lost. Further, INV2.0 decreased average operating time of the relays (15 - 25) when compared to INV1.2 at the expense of more miscoordination events. In all the simulated cases, the mean time of operation of the relays was 0.80 s (strong grids), 1.10 s (medium grids), and 1.50 s (weak grids). These findings affirm that, the level of protection coordination is becoming more sensitive to network impedance and relay settings as the level of PV penetration and inverter current capacity rises. The results highlight that conventional fixed-setting relays cannot be used in high-renewable systems and that adaptive or AI-aided protection coordination is needed to maintain system reliability and selectivity.
- Alqahtani, M.H., Draz, A., Shaheen, A.M. and El-Fergany, A.A. (2024) Advanced Relay Coordination in Power Networks Considering Transformer Inrush and Motor Starting Currents via Weighted Mean Variance Optimizer. IEEE Access , 12, 184953-184975. https://doi.org/10.1109/access.2024.3511698
- Altaf, M.W., Arif, M.T., Islam, S.N. and Haque, M.E. (2022) Microgrid Protection Challenges and Mitigation Approaches—A Comprehensive Review. IEEE Access , 10, 38895-38922. https://doi.org/10.1109/access.2022.3165011
- Farahani, A.A. and Sadeghi, S.H.H. (2021) The Use of NSGA-II for Optimal Placement and Management of Renewable Energy Sources When Considering Network Uncertainty and Fault Current Limiters. 2021 29 th Iranian Conference on Electrical Engineering ( ICEE ), Tehran, 18-20 May 2021, 437-442. https://doi.org/10.1109/icee52715.2021.9544336
- Singh, P., Kumar, U., Choudhary, N.K. and Singh, N. (2024) Advancements in Protection Coordination of Microgrids: A Comprehensive Review of Protection Challenges and Mitigation Schemes for Grid Stability. Protection and Control of Modern Power Systems , 9, 156-183. https://doi.org/10.23919/pcmp.2023.000250
- Vygoder, M., Banihashemi, F., Gudex, J., Eggebeen, A., Oriti, G. and Cuzner, R.M. (2024) A Novel Protection Design Process to Increase Microgrid Resilience. IEEE Transactions on Industry Applications , 60, 5372-5387. https://doi.org/10.1109/tia.2024.3377171
- Vegunta, S.C., Higginson, M.J., Kenarangui, Y.E., Li, G.T., Zabel, D.W., Tasdighi, M., et al. (2021) AC Microgrid Protection System Design Challenges—A Practical Experience. Energies , 14, Article 2016. https://doi.org/10.3390/en14072016
- Jawad Abed, M., A. Shalash, N. and Mhalla, A. (2024) Reliability Assessment of PV Location Based on a New Coordination and Failure Rates of Protection Relays to Minimize Indices Energy. Cogent Engineering , 11, Article 2340301. https://doi.org/10.1080/23311916.2024.2340301
- Adeosun, O.D. (2024) Addressing Protection Challenges in Electric Power Grids with Distributed Generation: A Focus on Directional Overcurrent Relays, Doctoral Dissertation, The University of North Carolina at Charlotte.
- Rezaei, F., Gandomkar, M. and Nikoukar, J. (2024) Optimizing Multi-Objective Function for User-Defined Characteristics Relays and Size of Fault Current Limiters in Radial Networks with Renewable Energy Sources. Journal of Operation and Automation in Power Engineering , 12, 42-53.
- Alhadrawi, A., Kamoona, A. and AlKhafaji, A. (2025) Smart Grid-Based Solutions to Prevent System Challenges Arising from the PV Integration in Power Networks. Engineering , Technology & Applied Science Research , 15, 26777-26782.