Load Shedding Application within a Microgrid to Assure Its Dynamic Performance during Its Transition to the Islanded Mode of Operation
- 1 Department of Electric Power and Automation Engineering, University of S?o Paulo, S?o Paulo, Brazil
- 2 Department of Electric Power and Automation Engineering, University of S?o Paulo, S?o Paulo, Brazil
- 3 FDTE (Foundation for the Technological Development of the Engineering Sciences), S?o Paulo, Brazil
Abstract
This article presents the simulation results and analysis related to the response of the generators within a microgrid towards an accidental overload condition that will require some load shedding action. A microgrid overload can occur due to various reasons ranging from poor load schedule, inadequate switching of circuits within the microgrid, outage of one or more generators inside the microgrid, illegal load connections by some low voltage consumers, etc. It was observed that among the main factors that determine the survival of the microgrid during its transition from the grid connected mode to the islanded mode of operation are the size and type of the load connected (passive or dynamic load) as well as the length of time during which the unexpected load is connected. Models of a speed and voltage regulators of a diesel generator, and important for coping with the overload conditions are provided in the paper. The novelty of the work lies in the load shedding simulation and analysis of the specific generators studied herein, regarding that in many countries the microgrid technology is seen as an important alternative towards the ever increasing load demand and also to assist the system during periods of blackout.
- W. C. New, J. Berdy, P. G. Brown and L. E. Goff, “Load Shedding, Load Restoration, and Generator Protection Using Solid-State and Electromechanical Underfrequency Relays,” General Electric Co. Pub. GET-6449, 1974, pp. 1-32. http://store.gedigitalenergy.com/FAQ/Documents/489/GET-6449.pdf
- C. R. Rowland, D. W. Smaha and J. W. Pope, “Coordina tion of Load Conservation with Turbine-Generator Un derfrequency Protection,” IEEE Transaction on Power Apparatus and Systems, Vol. 99, No. 3, 1980, pp. 1137-1150.
- M. S. Baldwin and H. S. Schenkel, “Determination of Frequency Decay Rates During Periods of Generation Deficiency,” IEEE Transactions on Power Apparatus and Systems, Vol. 95, No. 1, 1976, pp. 26-36. doi:10.1109/T-PAS.1976.32074
- M. Begovic, et al., “System Protection and Voltage Sta bility,” IEEE Transactions on Power Delivery, Vol. 10, No. 2, 1995, pp. 631-637. doi:10.1109/61.400868
- H. A. Bauman, G. R. Hahn and C. N. Metcalf, “The Ef fect of Frequency Reduction on Plant Capacity and on System Operation,” AIEE Transactions on Power Appa ratus and Systems, Vol. 74, 1955. pp. 1632-1637.
- S. A. Niremberg, D. A. McInnis and K. D. Sparks, “Fast Acting Load Shedding,” IEEE Transactions on Power Systems, Vol. 7, No. 2, 1992, pp. 873-877. doi:10.1109/59.141798
- T. Q. Tuan, J. Fandino, N. Hadjsaid, J. C. Sabonnadiere and H. Vu, “Emergency Load Shedding to Avoid Risks of Voltage Instability Using Indicators,” IEEE Transactions on Power Systems, Vol. 9, No. 1, 1994, pp. 341-351. doi:10.1109/59.317592
- V. V. Terzija, “Adaptive Under-Frequency Load Shed ding Based on the Magnitude of the Disturbance Estimation,” IEEE Transactions on Power Systems, Vol. 21, No. 3, 2006. pp. 1260-1266. doi:10.1109/TPWRS.2006.879315
- X. Xiong and W. Li, “A New Under-Frequency Load Shedding Scheme Considering Load Frequency Characteristics,” International Conference on Power System Technology, Chongqing, 22-26 October 2006, pp. 1-4.
- D. K. Singh, R. Shekhar and P. K. Kalra, “Optimal Load Shedding: An Economic Approach,” 2010 IEEE Region 10 Conference, Fukuoka, 21-24 November 2010, pp. 636-639.
- P. Mahat, C. Zhe and B. Bak-Jensen, “Underfrequency Load Shedding for an Islanded Distribution System with Distributed Generators,” IEEE Transactions on Power Delivery, Vol. 25, No. 2, 2010. pp. 911-918. doi:10.1109/TPWRD.2009.2032327
- D. Prasetijo, W. R. Lachs and D. Sutanto, “A New Load Shedding Scheme for Limiting Underfrequency,” IEEE Transactions on Power Systems, Vol. 9, No. 3, 1994. pp. 1371-1378. doi:10.1109/59.336128