PCHD-Based Passivity Control of VSC-HVDC Connected Large Wind Farm
- 1 School of Electric Power, South China University of Technology, Guangzhou, China
- 2 School of Electric Power, South China University of Technology, Guangzhou, China
- 3 School of Electric Power, South China University of Technology, Guangzhou, China
- 4 School of Electric Power, South China University of Technology, Guangzhou, China
- 5 Electric Power Research Institute, CSG, Guangzhou, China
- 6 Electric Power Research Institute, CSG, Guangzhou, China
Abstract
Concentrated integration of large scale wind power demands stronger robustness of VSC-HVDC transmission. Based on PCHD (Port Controled Hamiltonian with Dissipation) equation, the PCHD model of voltage source converter (VSC) in abc frame and d-q rotating frame are built and the strict passivity of VSC is proved. Desired energy function is constructed and used as Lyapunov function by assigning link matrix and damping matrix. Impact from VSC equivalent dc resistance is eliminated by additional damping matrix. The IDA-PB (Interconnection and Damping Assignment Passivity-based) controller is designed based on desired equilibrium point and state variable. With different operation conditions, VSC-HVDC and its control system are simulated by software PSCAD/EMTDC, the results show the proposed control strategy has good performance and strong robustness.
- L. Y. Zhang, T. L. Ye, Y. Z. Xin, et al, “Problems and Measures of Power Grid Accommodating Large Scale Wind Power,” Proceedings of the CSEE, Vol. 30, No. 25, 2010, pp. 1-9.
- N. Flourentzou, V. G. Agelidis and G. D. Demetriades, “VSC-based HVDC Power Transmission Systems: An Overview,” IEEE Transactions on Power Electronics, Vol. 24, No. 3, 2009, pp. 594-599. doi:10.1109/TPEL.2008.2008441
- S. M. Muyeen, R. Takahashi and J. Tamura, “Operation and Control of HVDC-connected Offshore Wind Farm,” IEEE Transactions on Sustainable Energy, Vol. 1, No. 1, 2010, pp. 30-37. doi:10.1109/TSTE.2010.2041561
- P. Bresesti, W. L. Kling and R. L. Hendriks, “HVDC Connection of Offshore Wind Farms to the Transmission System,” IEEE Transactions on Energy Conversion, Vol. 22, No. 1, 2007, pp. 37-43. doi:10.1109/TEC.2006.889624
- A. Moharana and P. K. Dash, “Input-output Linearization and Robust Sliding-mode Controller for the VSC-HVDC Transmission Link,” IEEE Transactions on Power Delivery, Vol. 25, No. 3, 2010, pp. 1952-1961. doi:10.1109/TPWRD.2010.2042469
- L. D. Zhang, L. Harnefors and H. P. Nee, “Interconnection of Two Very Weak AC Systems by VSC-HVDC Links Using Power Synchronization Control,” IEEE Transactions on Power Systems, Vol. 26, No. 2, 2011, pp. 345-347.
- M. Y. Guan and Z. Xu, “Modeling and Control of Modular Multilevel Converter in HVDC Transmission,” Automation of Electric Power Systems, Vol. 34, No. 19, 2010, pp. 64-68.
- S. Y. Ruan, G. J. Li, X. H. Jiao, et al., “Adaptive Control Design for VSC-HVDC Systems Based on Backstepping Method,” Electric Power Systems Research, Vol. 77, No. 6, 2007, pp. 559-565. doi:10.1016/j.epsr.2006.05.006
- S. H. Li, T. A. Haskew and L. Xu, “Control of HVDC Light System Using Conventional and Direct Current Vector Control Approaches,” IEEE Transactions on Power Electronics, Vol. 25, No. 12, 2010, pp. 3106-3118. doi:10.1109/TPEL.2010.2087363
- S. Li, Z. X. Wang, G. Q. Wang, et al., “PID Neural Network Sliding-mode Controller for Three-level Offshore Wind Power VSC-HVDC Converter,” Proceedings of the CSEE, Vol. 32, No. 4, 2012, pp. 20-28.
- R. Ortega and G. C. Eloísa, “Interconnection and Damping Assignment Passivity-based Control: A Survey,” European Journal of Control, Vol. 10, No. 5, 2004, pp. 1-27. doi:10.3166/ejc.10.432-450
- T. S. Lee, “Lagrangian Modeling and Passivity Based Control of Three-phase AC/DC Voltage-source Converters,” IEEE Transaction on Industrial Electronics, Vol. 51, No. 4, 2004, pp. 892-902. doi:10.1109/TIE.2004.831753