Measurement and Simulation of Induced Voltage and Current on 110 KV Crossing Transmission Lines under UHV AC Transmission Lines
- 1 State Grid Jinhua Power Supply Company, Jinhua, China
- 2 State Grid Jinhua Power Supply Company, Jinhua, China
- 3 China Electric Power Research Institute, Wuhan, China
- 4 China Electric Power Research Institute, Wuhan, China
- 5 School of Electrical Engineering, Wuhan University, Wuhan, China
Abstract
The induced electricity of 110 kV transmission lines which cross the UHV AC transmission lines may threaten personal safety of the maintenance staff. In this paper, field measurement of the induced voltage and induced current on a 110 kV crossing line inside Jinhua in Zhejiang province is performed. The electrostatic induced voltage on the measured line is 12.24 kV. The power frequency electromagnetic field simulation model is established, and the calculation results are consistent with the measured. Influence factors analysis shows that the electrostatic induced voltage on the 110 kV line is 12.78 kV, the electromagnetic induced voltage is 12.3 V, the induced current through ground wire is less than 1A when the UHV lines operate at full load. The induced voltage and current decrease while the crossing distance increases. Parallel lines induction is much higher than crossing lines. The electromagnetic induced voltage after ground knife-switch shut down would exceed the human safety voltage 36 V while the crossing angle is less than 30?, so the temporary ground wire must be hanged to ensure safety of the maintenance staff.
- Liu, Z.Y. (2013) Innovation of UHVAC Transmission Technology in China. Power System Technology, 37, T1-T8.
- Liu, Z.Y. (2013) UHVAC/DC Power Grid. China Electric Power Press, Beijing.
- Shu, Y.B. and Zhang, W.L. (2007) Research of Key Technologies for UHV Transmission. Proceedings of the CSEE, 27, 1-6.
- Xiao, D.P., Jiang, K.R., Zhang, Z.L., et al. (2015) Optimization Algorithm for Arranging Extra-and Ultra-High Voltage Transmission Lines Subjected to the Constraints of Power Fre-quency Electromagnetic Environment Condition. Proceedings of the CSEE, 35, 2333-2341.
- Hu, S.S., Li, J., Ma, L., et al. (2012) Ground Clearance and Crossing Clearance of ±1100 kV UHVDC Transmission Line. Electric Power Construction, 33, 25-28.
- Tanen, J.D. and Wilson, G.L. (1971) Electrostatically Induced Voltages and Currents on Conducting Objects under EHV Transmission Lines. IEEE Transactions on Power Apparatus and Systems, 90, 341-349.
- Lin, C., Chuang, H. and Chen, K. (1990) Steady-state and Shock Currents Induced by ELF Electric Fields in a Human Body and a Nearby Vehicle. IEEE Transactions on Electromagnetic Compatibility, 32, 59-65. https://doi.org/10.1109/15.45251
- Wang, C.Y. (2010) The Reason and Protection Measurement of" Induced Electricity" inTransmission Lines Maintanence. Electrical Security Technology, 12, 6-12.
- Hu, D.H., Tu, C.Q., Jiang, W., et al. (2008) Calculation of Inductive Voltage and Current for 500 kv Double Circuits Transmission Lines on Single Tower. High Voltage Engineering, 34, 1927-1931.
- Guo, Z.H., Yao, J.X., Cheng, X.Q, et al. (2006) StudyandMeasure-mentofInducedVoltageandCurrentfor500kVDoublyCircuitLineonSameTower.HighVoltageEngineering, 32, 11-14,50.
- Li, B.J. and Zhou, H. (2011) Calculation and Analysis on Induced Voltage and Current of 1000 kV Transmission Line Adopting Structure of Double Circuit on the Same Tower. Power System Technology, 35, 14-19.
- Liu, H.J, Yan, G.Z., Wang, S.H, et al. (2015) Analysis of Electrostatic Induced Voltageon1000 kV Wannan-Zhebei UHVAC Transmission Line. High Voltage Engineering, 41, 1687-1693.
- Li, Z.Q., Liu, C.Q., Dai, M., et al. (2013) Induced Voltage and Induced Current on AC Same-Tower Four-Circuit Lines Comprised of Double-Circuit 1000 kV Lines and Double-circuit 500 kV or 220 kV Lines. High Voltage Engineering, 39, 3022-3028.