Reaction Rate Characteristics of SrBr<sub>2</sub> Hydration System for Chemical Heat Pump Cooling Mode
- 1 Department of Chemical Engineering, Nagoya University, Nagoya, Japan
- 2 Department of Chemical Engineering, Nagoya University, Nagoya, Japan
Abstract
Here, we propose a chemical heat pump chiller with a SrBr 2 hydration reaction system for utilization of waste heat. The SrBr 2 hydration reaction could recover waste heat in low temperatures ranging from 373 K to 353 K, and the system showed good potential in terms of the high cooling thermal-storage density. Previous studies have given little information on the reaction characteristics of the SrBr 2 hydration reaction. In this paper, we developed a measuring method for the hydration reaction equilibrium and reaction rate based on the volumetric method. We analyzed the hydration reaction rate with an unreacted-core shell model. In the experiments, the SrBr 2 equilibrium temperature observed was equal to the theoretical equilibrium temperature obtained from thermodynamic databases. In addition, the hysteresis gap between the hydration and dehydration values was 2.0 K. Thus, the hysteresis effect was negligible for the chemical heat pump cooling operation. The reaction fraction of the SrBr 2 hydration reached 0.7 within 20 s. By analyzing the hydration reaction rate with the unreacted-core shell model, the activation energy value was calculated to be56.6 kJ/mol. The calculation results showed good agreement with those of the experiment as the reaction fraction reached 0.7.
- Kato, Y., Kobayashi, K. and Yoshizawa, Y. (1998) Durability to Repetitive Reaction of Magnesium Oxide/Water Reaction System for a Heat Pump. Applied Thermal Engineering, 18, 85-92. http://dx.doi.org/10.1016/S1359-4311(97)00058-6
- Abliz, S., Ogura, H., Kage, H. and Matsuno, Y. (2002) Kinetic Study of CaO/Ca(OH)2 reversible Chemical Reaction in Vacuumed Forced Convection for Thermal Energy Storage. Kagaku Kogaku Ronbunshu (Japan), 28, 345-349. http://dx.doi.org/10.1252/kakoronbunshu.28.345
- Abedin, A.H. and Rosen, M.A. (2012) Closed and Open Thermochemical Energy Storage: Energy- and Exergy-Based Comparisons. Energy, 41, 83-92. http://dx.doi.org/10.1016/j.energy.2011.06.034
- Ogura, H., Kubota, M., Suzuki, H. and Yazawa, T. (2009) Fundamental Experimental Study on Chemical Heat Pump for storing Low-Temperature Waste Heat and Releasing Cold-Heat. Kagaku Kogaku Ronbunshu (Japan), 35, 506-510. http://dx.doi.org/10.1252/kakoronbunshu.35.506
- Mauran, S., Lahmidi, V. and Goetz, V. (2008) Solar Heating and Cooling by a Thermochemical Process. First Experiments of a Prototype Storing 60kW h by a Solid/Gas Reaction. Solar Energy, 82, 623-636. http://dx.doi.org/10.1016/j.solener.2008.01.002
- Lahmidi, H., Mauran, S. and Goetz, V. (2006) Definition, Test and Simulation of Thermochemical Storage Process Adapted to Solar Thermal Systems. Solar Energy, 80, 883-893. http://dx.doi.org/10.1016/j.solener.2005.01.014
- Matsuda, H., Ishizu, T., Lee, S.K. and Hasatani, M. (1985) Kinetic Study of Ca(OH)2/CaO Reversible Thermochemical Reaction for Thermal Energy Storage by Means of Chemical Reaction. Kagaku Kogaku Ronbunshu (Japan), 11, 542-548. http://dx.doi.org/10.1252/kakoronbunshu.11.542
- Kubota, M., Kyaw, K., Watanabe, F., Matsuda, H. and Hasatani, M. (2000) Study of Decarbonation of CaCO3 for High Temperature Thermal Energy Storage. Journal of Chemical Engineering Japan, 33, 797-800. http://dx.doi.org/10.1252/jcej.33.797
- Ogura, H., Haguro, M., Shibata, Y. and Otsubo, Y. (2007) Reaction Characteristics of CaSO4/CaSO4•1/2H2O Reversible Reaction for Chemical Heat Pump. Journal of Chemical Engineering Japan, 40, 1252-1256. http://dx.doi.org/10.1252/jcej.07WE223